Wednesday, September 16, 2020

Output filters : Sinus filters

Variable speed drives 
Altivar Process 
Option: Output filters Sinus filters




Sinus filters allow Altivar Process drives to operate with long motor cables:
  • 500 m (1,640 ft) with a shielded cable
  • 1,000 m (3,280 ft) with an unshielded cable
The minimum switching frequency at which sinus filters can operate is 4 kHz. This is the default value when the sinus filter function is activated on the variable speed drive. 
The output frequency must be less than 100 Hz.
At 100% load, the voltage drop is less than 8% with output frequency 50 Hz and switching frequency 2 kHz.
For applications requiring:
  • Long cable runs
  • Motors connected in parallel
  • Submersible pumps sensitive to dv/dt
  • An intermediate transformer between the drive and the motor